Crown Micro CMUO-10KVA 10kVA 10kW Online Double Conversion UPS
SKU: CMUO-10KVA
The CMUO-10KVA is a 10 kVA / 10 kW online double conversion UPS with output PF 1.0, active PFC and settable 3:1 or 1:1 input. It comes as a long backup model for external batteries or a standard model with internal battery space.
Tell us about your project and we will recommend the right equipment.
Talk to an advisorKey features
Official warranty: 1 year
- Rated capacity:10 kVA / 10 kW
- Output power factor:1.0
- Input voltage, full load:304 - 478 Vac (L-L)
- Efficiency (online / ECO):Max. 94.5% / up to 98%
- Battery voltage:192 Vdc
- Battery quantity:16 - 20 pcs (settable)
- Max. charging current:10 A
- Operating temperature:0 - 40 °C
Crown Micro - CMUO series online UPS
CMUO-10KVA Online UPS 10 kVA / 10 kW double conversion
The CMUO-10KVA is an online double conversion UPS that supplies critical loads with a clean, regulated sine output at unity power factor. It combines DSP control, active power factor correction and a wide input window, so it suits installers protecting sensitive equipment on unstable mains. It is offered as a long backup model for external batteries or as a standard model with internal battery space.
- 10 kVA / 10 kW
- Output PF 1.0
- 3:1 or 1:1 input
- Optional digital parallel
- Cold start on battery
- 10 kVA
- Rated capacity (10 kW)
- 1.0 PF
- Output power factor
- 98 %
- ECO mode efficiency
- 10 A
- Max. charging current
The CMUO-10KVA online UPS delivers 10 kVA / 10 kW at an output power factor of 1.0 through online double conversion with advanced DSP control and 3-level technology. Output voltage regulation is ± 1% and THDv stays below 1% on a full linear load.
On the input side, the CMUO-10KVA accepts 304 to 478 Vac (L-L) at full load, with linear derating down to 190 Vac, and an input power factor above 0.99 thanks to active PFC. The input configuration is settable as 3:1 or 1:1, and the battery string can be set from 16 to 20 batteries with a charger of up to 10 A.
Technology features
- ControlDSP and 3-level technology Online double conversion with DSP control keeps the output at power factor 1.0, with ± 1% regulation and THDv below 1% on linear load.
- InputWide window and active PFC The UPS works from 304 to 478 Vac (L-L) at full load and 40 to 70 Hz, with an input power factor above 0.99.
- ConfigurationFlexible input and output Settable 3:1 or 1:1 input, dual input with independent bypass, 50 / 60 Hz conversion and optional digital parallel.
- BatteriesIntelligent management The charger delivers up to 10 A for 16 to 20 settable batteries, with smart float and equalize charging and dormancy control that extends battery life by up to 50%.
- OperationSmart supervision Temperature-controlled fan speed, LCD and LED display, cold start on battery, self-aging and full self-diagnostics with an event log.
- ConnectivityCommunication options RS-232 and a smart slot come as standard, with optional USB, RS-485, SNMP, dry contacts, EMD, SMS alarms and battery temperature compensation. Conformal coating supports long operation in harsh environments.
Model versions and configurations
Technical specifications
| Long backup (H) battery | External battery bank |
|---|---|
| Long backup (H) dimensions (W x D x H) | 191 x 495 x 350 mm |
| Long backup (H) weight | 18.5 kg |
| Standard (S) battery | Internal battery space |
| Standard (S) dimensions (W x D x H) | 191 x 495 x 711 mm |
| Standard (S) weight | 64 kg |
| Rated capacity | 10 kVA / 10 kW (PF 1) |
|---|---|
| Configuration | 3:1 / 1:1 settable |
| Voltage, full load | 304 to 478 Vac (L-L) |
| Voltage, derated | 190 to 304 Vac (L-L), linear |
| Input current | 20 A / 380 V |
| Frequency | 40 to 70 Hz (50 / 60 Hz auto-sense) |
| Power factor | > 0.99 (full load) |
| Bypass | Dual input, independent bypass |
| Output voltage | 220 / 230 / 240 Vac (L-N) |
|---|---|
| Output current | 45.5 A |
| Voltage regulation / PF | ± 1% / 1.0 |
| Frequency tolerance | ± 0.1% of nominal |
| THDv | < 1% (full linear load) |
| Overload 110% / 130% | To bypass after 60 min / 1 min |
| Overload 150% | To bypass after 30 s, off after 1 min |
| Crest factor | 3:1 maximum |
| Efficiency (online / ECO) | Max. 94.5% / up to 98% |
| Battery voltage | 192 Vdc |
|---|---|
| Battery quantity | 16 to 20 pcs (settable) |
| Battery current / charging | Max. 67 A / max. 10 A |
| Communication | RS-232, slot; optional USB, RS-485, SNMP |
| Display | LCD + LED |
| Operating temperature | 0 to 40 °C |
|---|---|
| Humidity / altitude | < 95% / < 1000 m |
| Storage temperature | 0 to 70 °C |
| 1000 m | 100% |
|---|---|
| 1500 m | 95% |
| 2000 m | 91% |
| 2500 m | 86% |
| 3000 m | 82% |
| 3500 m | 78% |
| 4000 m | 74% |
| 4500 m | 70% |
| 5000 m | 67% |
Integration segments
- Server rooms and IT equipment Double conversion output at PF 1.0 with THDv below 1% on linear load protects sensitive electronics.
- Industrial control and process loads The 3:1 maximum crest factor and conformal coating suit demanding loads in tough conditions.
- Commercial and office buildings The wide 304 to 478 Vac input window helps keep critical circuits running on variable mains.
- Extended-autonomy backup systems The long backup version works with an external battery bank, with a 16 to 20 battery string settable from the UPS.
Global backing
Crown Micro: energy engineering with global backing.
- More than 30 years of international experience in energy solutions
- Commercial presence in more than 15 countries on four continents
- Product lines with international certifications
- Specialized technical support and after-sales engineering
- Personalized commercial advice for residential and productive projects
Frequently asked questions
What output power does the CMUO-10KVA provide?
The CMUO-10KVA is rated at 10 kVA / 10 kW with an output power factor of 1.0. Output current is 45.5 A and the output voltage is selectable among 220, 230 and 240 Vac (L-N).
What input voltage range does the CMUO-10KVA accept?
At full load the input range is 304 to 478 Vac (L-L). Below that, the UPS derates linearly from 304 down to 190 Vac (L-L). The input frequency range is 40 to 70 Hz with 50 / 60 Hz auto-sensing.
Can the input configuration be changed?
Yes. The input configuration is settable as 3:1 or 1:1. The UPS also has a dual input with an independent bypass.
How many batteries does the CMUO-10KVA use and how fast does it charge them?
The battery voltage is 192 Vdc and the number of batteries is settable from 16 to 20 pcs. The charging current is up to 10 A, while the maximum battery current is 67 A.
What is the difference between the long backup (H) and standard (S) versions?
The long backup (H) version works with an external battery bank and weighs 18.5 kg, measuring 191 x 495 x 350 mm (W x D x H). The standard (S) version has internal battery space and weighs 64 kg, measuring 191 x 495 x 711 mm (W x D x H).
How does the CMUO-10KVA behave on overload?
At 110% and 130% load, the UPS transfers to bypass after 60 min and 1 min respectively. At 150% load, it transfers to bypass after 30 s and turns off after 1 min.
Does altitude affect the output power?
Yes. Full output power is available up to 1000 m and is derated above that: 95% at 1500 m, 91% at 2000 m, 82% at 3000 m and 67% at 5000 m. The operating temperature range is 0 to 40 °C.