Crown Micro CMUO-20KVA 20kVA 20kW Online Double Conversion UPS
SKU: CMUO-20KVA
The CMUO-20KVA is a 20 kVA / 20 kW online double conversion UPS with output PF 1.0, settable 3:1 or 1:1 input and a long backup design for external battery banks.
Cuéntanos tu proyecto y te recomendamos el equipo adecuado.
Hablar con un asesorCaracterísticas destacadas
Garantía oficial: 1 año
- Rated capacity:20 kVA / 20 kW
- Output power factor:1.0
- Efficiency (online / ECO):Max. 95% / up to 98%
- Input voltage at full load:304 - 478 Vac (L-L)
- Battery voltage:192 Vdc
- Max. charging current:10 A
- Dimensions (W × D × H):191 × 495 × 515 mm
- Weight:26.5 kg
Crown Micro - Online UPS, CMUO series
CMUO-20KVA online UPS 20 kVA / 20 kW, PF 1.0
The CMUO-20KVA is an online double conversion UPS with DSP control and 3-level technology, built to protect critical loads with a unity output power factor. It is a long backup model that works with an external battery bank, for installers and buyers who need extended autonomy.
- 20 kVA / 20 kW
- Output PF 1.0
- 3:1 / 1:1 settable
- Long backup model
- Parallel (optional)
- 20 kVA
- Rated capacity (20 kW)
- 1.0 PF
- Output power factor
- 98 %
- ECO mode efficiency
- 10 A
- Max. charging current
The CMUO-20KVA online UPS delivers 20 kVA / 20 kW at an output power factor of 1.0 through online double conversion with advanced DSP control. Output regulation is ± 1% and voltage distortion (THDv) stays below 1% on a full linear load, with efficiency of max. 95% in online mode and up to 98% in ECO mode.
Active power factor correction keeps the input power factor above 0.99, and the input accepts 304 to 478 Vac (L-L) at full load. The input configuration can be set to 3:1 or 1:1, and the unit uses an external battery bank of 16 to 20 batteries, charged at up to 10 A. Conformal coating technology helps the UPS operate for long periods in harsh environments.
Technology features
- ControlDSP and 3-level technology The CMUO-20KVA uses advanced DSP control with 3-level technology. Rectification and inversion are managed by dual DSP.
- InputWide input range and APFC The input accepts 304 to 478 Vac (L-L) at full load and 190 to 304 Vac with linear derating, at 40 to 70 Hz. Input power factor is above 0.99.
- Configuration3:1 or 1:1 settable Dual input with an independent bypass, 50 / 60 Hz conversion and optional digital parallel operation.
- BatteryIntelligent battery management The charger delivers up to 10 A with smart float and equalize charging. Dormancy control extends battery life by up to 50%, and 16 to 20 batteries can be set.
- OperationSmart operation Temperature-controlled fan speed, LCD and LED display, cold start on battery, self-aging and full self-diagnostics with an event log.
- ConnectivityCommunication options RS-232 and an intelligent slot come as standard. USB, RS-485, SNMP, dry contacts, EMD, SMS alarms and battery temperature compensation are optional.
Operating configurations
Technical specifications
| Version | Long backup (H) |
|---|---|
| Battery | External battery bank |
| Dimensions (W × D × H) | 191 × 495 × 515 mm |
| Weight | 26.5 kg |
| Rated capacity | 20 kVA / 20 kW (PF 1) |
|---|---|
| Configuration | 3:1 / 1:1 settable |
| Voltage, full load | 304 - 478 Vac (L-L) |
| Voltage, derated | 190 - 304 Vac (L-L), linear |
| Input current | 40 A / 380 V |
| Frequency | 40 - 70 Hz (50 / 60 Hz auto-sense) |
| Power factor | > 0.99 (full load) |
| Bypass | Dual input, independent bypass |
| Output voltage | 220 / 230 / 240 Vac (L-N) |
|---|---|
| Output current | 91 A |
| Voltage regulation / PF | ± 1% / 1.0 |
| Frequency tolerance | ± 0.1% of nominal |
| THDv | < 1% (full linear load) |
| Overload 110% / 130% | To bypass after 60 min / 1 min |
| Overload 150% | To bypass after 30 s, off after 1 min |
| Crest factor | 3:1 maximum |
| Efficiency (online / ECO) | Max. 95% / up to 98% |
| Battery voltage | 192 Vdc |
|---|---|
| Battery quantity | 16 - 20 pcs (settable) |
| Battery current / charging | Max. 134 A / max. 10 A |
| Communication | RS-232, slot; opt. USB, RS-485, SNMP |
| Display | LCD + LED |
| Operating temperature | 0 - 40 °C |
|---|---|
| Humidity / altitude | < 95% / < 1000 m |
| Storage temperature | 0 - 70 °C |
| 1000 m | 100% |
|---|---|
| 1500 m | 95% |
| 2000 m | 91% |
| 2500 m | 86% |
| 3000 m | 82% |
| 3500 m | 78% |
| 4000 m | 74% |
| 4500 m | 70% |
| 5000 m | 67% |
Integration segments
- Server rooms and IT infrastructure Clean, regulated power with a unity power factor for servers, storage and network equipment.
- Industrial and process control Protection for control systems that cannot tolerate supply interruptions, with conformal coating for harsh environments.
- Medical and laboratory equipment Continuous power for sensitive instruments, with long autonomy from an external battery bank.
- Telecom and communication sites Stable supply for communication equipment, with 50 / 60 Hz conversion and remote monitoring options.
Global backing
Crown Micro: energy engineering with global backing.
- More than 30 years of international experience in energy solutions
- Commercial presence in more than 15 countries on four continents
- Product lines with international certifications
- Specialized technical support and after-sales engineering
- Personalized commercial advice for residential and productive projects
- Sales contact through crownmicroglobal.com and info@crownmicroglobal.com
Preguntas frecuentes
What load can the CMUO-20KVA support?
The CMUO-20KVA is rated 20 kVA / 20 kW because its output power factor is 1.0. Output current is 91 A, and output voltage can be 220, 230 or 240 Vac (L-N).
Does the UPS include batteries?
No. The CMUO-20KVA is a long backup model designed for an external battery bank. The battery voltage is 192 Vdc, and 16 to 20 batteries can be set.
How fast does the UPS charge the batteries?
The charger delivers a maximum of 10 A, with smart float and equalize charging. Maximum battery current is 134 A.
What input voltage and frequency does it accept?
At full load the input range is 304 to 478 Vac (L-L). It derates linearly down to 190 Vac, and accepts 40 to 70 Hz with 50 / 60 Hz auto-sensing. Input power factor is above 0.99.
How does the UPS behave under overload?
At 110% load it transfers to bypass after 60 minutes, and at 130% after 1 minute. At 150% it goes to bypass after 30 seconds and switches off after 1 minute.
Does altitude affect the output power?
Yes. Output power is 100% up to 1000 m, 91% at 2000 m, 82% at 3000 m and 67% at 5000 m. The operating humidity and altitude rating is below 95% and below 1000 m.
What communication options are available?
RS-232 and an intelligent slot come as standard. USB, RS-485, SNMP, dry contacts, EMD, SMS alarms and battery temperature compensation are optional, and the unit has an LCD and LED display.