Crown Micro CMUO-3KVA 3kVA 2700W Online Double Conversion UPS
SKU: CMUO-3KVA
The CMUO-3KVA is a 3 kVA / 2700 W high-frequency online double conversion UPS with 0 ms transfer, 110 to 300 Vac input and an LCD. It comes in standard and long backup versions.
Cuéntanos tu proyecto y te recomendamos el equipo adecuado.
Hablar con un asesorCaracterísticas destacadas
Garantía oficial: 1 año
- Rated capacity:3 kVA / 2700 W
- Output power factor:0.9
- Input voltage range:110 - 300 Vac
- Transfer mains to battery:0 ms
- Efficiency (line / battery / ECO):92% / 87% / 97%
- Voltage accuracy:± 1%
- Battery type:Sealed lead acid, maintenance free
- Communication:RS-232; optional USB, SNMP, dry contacts
Crown Micro - CMUO series online UPS
CMUO-3KVA Online UPS 3 kVA / 2700 W
The CMUO-3KVA is a high-frequency online double conversion UPS with DSP control and active power factor correction. It gives critical loads a regulated pure output with 0 ms transfer to battery, even on unstable mains. It is offered as a standard model with internal batteries or as a long backup model for external battery banks.
- 3 kVA / 2700 W
- 0 ms transfer
- 110-300 Vac input
- LCD display
- Short and long backup
- 3 kVA
- Rated capacity (2700 W)
- 0 ms
- Transfer to battery
- 0.9
- Output power factor
- 97 %
- ECO mode efficiency
The CMUO-3KVA online UPS delivers 3 kVA / 2700 W at an output power factor of 0.9, with a voltage accuracy of ± 1% and a load crest factor of 3:1. Its high-frequency double conversion stage is managed by a DSP, and the input power factor correction reaches 0.99 or better with input current distortion of 6% or less.
A wide 110 to 300 Vac input range and auto-sensed 50 / 60 Hz operation let the CMUO-3KVA keep loads on mains power through large voltage swings before it draws on the battery. Two model families are available: standard (S) versions with internal sealed lead-acid batteries at 72 V or 96 V, and a long backup (L) version that connects to an external 96 V battery bank.
Technology features
- TopologyOnline double conversion High-frequency double conversion with DSP control gives a ± 1% output accuracy and THDv of 2% or less on linear loads.
- InputWide range and APFC The CMUO-3KVA accepts 110 to 300 Vac and 40 to 70 Hz, with active power factor correction of 0.99 or better and linear derating at low voltage to save battery.
- SettingsLCD settable functions Output voltage, end of discharge (EOD), auto-start, bypass mode, ECO mode and 50 / 60 Hz frequency conversion are set from the LCD.
- BatteryBattery management Quick and stable charging restores 90% of capacity in 3 to 4 h on standard models, with charging current up to 6 A / 3 A on long backup models.
- ProtectionFull protection set Over-temperature, fan testing, overload, output short-circuit and battery discharge protection are included, together with cold start.
- CommunicationMonitoring options RS-232 is standard. USB, RS-485, an SNMP card, AS400 dry contacts and an EPO function are optional.
Operating modes
Technical specifications
| Version | Standard (S) / Standard (S) / Long backup (L) |
|---|---|
| DC voltage | 72 V / 96 V / 96 V |
| Inbuilt battery | 12 V 9 Ah × 6 / 12 V 7 Ah × 8 / External (8 × 12 V) |
| Charger output voltage | 81.3 ± 1.2 V / 108.4 ± 1.6 V / 108.4 ± 1.6 V |
| Max. charging current | 1 A / 1 A / 6 A / 3 A |
| Dimensions (W × D × H) | 191 × 418 × 335 mm / 191 × 464 × 335 mm / 191 × 418 × 335 mm |
| Weight | 27.2 kg / 32 kg / 11 kg |
| Rated capacity | 3 kVA / 2700 W |
|---|---|
| Rated input voltage | 208 / 220 / 230 / 240 Vac |
| Rated input frequency | 50 / 60 Hz (auto-sense) |
| 110 - 176 Vac | Linear derating 50 - 100% load |
| 176 - 280 Vac | No derating |
| 280 - 300 Vac | Derating to 50% |
| Input frequency range | 40 - 70 Hz |
| PFC / THDi | ≥ 0.99 / ≤ 6% |
| Bypass voltage range | -25% to +15% (settable) |
| Output voltage | 208 / 220 / 230 / 240 Vac, settable |
|---|---|
| Voltage accuracy / output PF | ± 1% / 0.9 |
| Overload 105 - 125% | To bypass in 1 min |
| Overload 125 - 150% / > 150% | To bypass in 30 s / 300 ms |
| Load crest factor | 3:1 |
| Transfer mains to battery / bypass | 0 ms / ≤ 4 ms |
| Frequency (line / battery mode) | Same as input / 50 / 60 ± 0.1 Hz |
| THDv | ≤ 2% linear; ≤ 5% non-linear |
| Efficiency (line / battery / ECO) | 92% / 87% / 97% |
| Capacity derating | 70% in CVCF mode; 90% when output voltage is adjusted to 208 Vac |
| Battery type | Sealed lead acid, maintenance free |
|---|---|
| Recharging time | 90% in 3 h (standard models) |
| Protections | Over-temperature, fan, overload, short circuit, battery discharge |
| Communication port | RS-232; optional USB, SNMP, dry contacts |
| Display | LCD |
| Operating humidity | 0 - 90% RH at 0 - 40 °C |
|---|---|
| Storage temperature | -25 °C to 55 °C (excluding batteries) |
| Operating altitude | ≤ 1000 m (1% derating per 100 m) |
| Protection class | IP20 |
| Noise level | ≤ 50 dBA (at 1 m) |
Integration segments
- Critical electronic loads Regulated pure output with 0 ms transfer protects sensitive equipment during mains failures.
- Network and server equipment RS-232 as standard, with optional USB, RS-485, SNMP card and dry contacts for monitoring.
- Sites with unstable mains The 110 to 300 Vac input window keeps loads on mains power through wide voltage swings.
- Extended backup projects The long backup version charges an external 96 V battery bank for longer autonomy.
Global backing
Crown Micro: energy engineering with global backing.
- More than 30 years of international experience in energy solutions
- Commercial presence in more than 15 countries on four continents
- Product lines with international certifications
- Specialized technical support and after-sales engineering
- Personalized commercial advice for residential and productive projects
- Portfolio of inverters, lithium batteries, frequency drives, panels and kits
Preguntas frecuentes
What real power can the CMUO-3KVA supply?
The CMUO-3KVA is rated at 3 kVA / 2700 W with an output power factor of 0.9. Capacity derates to 70% in CVCF mode and to 90% when the output voltage is adjusted to 208 Vac.
What input voltage range does it accept?
The input range is 110 to 300 Vac at 40 to 70 Hz. There is no derating from 176 to 280 Vac, linear derating from 50 to 100% load between 110 and 176 Vac, and derating to 50% between 280 and 300 Vac.
How fast does the UPS switch to battery?
Transfer from mains to battery takes 0 ms. Transfer to bypass takes 4 ms or less.
What is the difference between the standard and long backup versions?
Standard (S) versions have internal sealed lead-acid batteries, at 72 V (12 V 9 Ah × 6) or 96 V (12 V 7 Ah × 8). The long backup (L) version uses an external 96 V bank of 8 × 12 V batteries and charges at up to 6 A / 3 A.
How long does the battery take to recharge?
On standard models the batteries recover 90% of their capacity in 3 h according to the technical table. The feature overview gives 3 to 4 h.
How can the CMUO-3KVA be monitored?
RS-232 is standard. USB, RS-485, an SNMP card, AS400 dry contacts and an EPO function are optional.
What are the operating environment limits?
Operating humidity is 0 to 90% RH at 0 to 40 °C, and altitude is up to 1000 m with 1% derating per 100 m. The protection class is IP20 and noise is 50 dBA or less at 1 m.